| Parameter
| Specifications
|
| Voltage and current measurements
| 4 fully differential channels
One AC/DC voltage channel and 3 voltage/current channels
0-600Vrms; 0-3000A, depending on current probe selected
Accuracy: ±1% reading ±0.2% full scale
|
| Impulse measurements
| 2.4 to 6144 Vpeak
2.4 to 6000 Amps pk
1 microsecond minimum duration
|
| Sampling rate
| 7.2kHz/channel for RMS
1.85MHz/channel for impulse
|
| Frequency
| Fundamental range 45 - 65 Hz
Optional Model 658-400 45-65Hz or 310-445 Hz
|
| Optional inputs
| 8 independent differential channels
Configurable as voltage or current
0-10Vdc, 0-20mA DC
Sampled at 12.5 Hz
|
| Environment
| 41°F to 104°F
+5°C to +40°C
Humidity 10% - 90% non-condensing
|
| Battery
| Standard
5 minutes operation typical
|
| PC Software package
| DranView
|
| Certifications
|
(CE certification for model 658E, UL listing for model 658)
|
| Latest released version
| 658 FEP V3.1
658 CPU V4.23
658 Front Panel INTFC V1.1
|