Fluke 43 Power Quality Analyzer
The Fluke 43 Power Quality Analyzer performs the measurements you need to
maintain power systems, troubleshoot power problems and diagnose equipment
failures. All in a rugged handheld package.
- Combines the most useful capabilities of a power quality analyzer,
multimeter and scope
- Measure power harmonics, and catch intermittents
- Monitoring functions help track intermittent problems and power system
performance
- Menus use familiar electrical terminology
- Complete package with voltage and current probes, PC software and
cable
- Applications manual, power quality video and users manual explain
measurements step-by-step
Features
- Voltage and current waveforms
- True-rms voltage and current
- Frequency
Power
- Watts, power factor, displacement power factor, VA and VAR
- Voltage and current waveforms
Harmonics
- Voltage, current, and power harmonics
- Up to 51st harmonic
- Total harmonic distortion (THD)
- Phase angle of individual harmonics
Sags & Swells
- Continuously measure volts and amps on a cycle-by-cycle basis for
up to 16 days
- Use cursors to read time and date of sags and swells
Transients
- Catch voltage transients and waveform distortion
- Catch and save up to 40 transients
- Correlate the cause of transient with time and date stamps
Inrush
- Inrush current up to 500A with supplied current probe
- Use cursors to measure inrush timing
Scope
- Connect-and-Viewª scope for quick waveform display
- Voltage and current channels
- 20 MHz bandwidth with optional 10:1 voltage probe. 15 kHz on current
channel with optional clamp
Specifications
|
General Specifications
|
|
Power
|
Line voltage adapter/battery charger included
Installed battery: Rechargeable Ni-Cd pack
Operating time: 4 hours
Charging time: 4 hours
|
|
Environmental
|
Temperature: 0¼C to 50¼C (32¼F to 122¼F)
Environmental: MIL 28800E, Type 3, Class III, Style B
Enclosure: IP51 (dust, drip water proof)
|
|
Mechanical Data
|
Size: (H x W x D) 232 x 115 x 50 mm (9.1 x 4.5 x 2
inches)
Weight: 1.1 kg (2.5 lbs)
|
|
Technical Data
|
|
Input Characteristics
|
Input impedance: 1 MW, 20 pF
Voltage Rating: 600V rms, CAT III
|
|
Volt/Amps/Hertz Display
|
True-rms voltage (ac+dc)
Ranges: 5.000V, 50.00V, 500.0V, 1250V*
Accuracy: ±(1% +10 counts)
True-rms current (ac + dc)
Ranges: 50.00A, 500.0A, 5.000 kA, 50.00 kA
Accuracy: ±(1% +10 counts)
Mains frequency
Ranges: 40.0 to 70.0 Hz
Accuracy: ±(0.5% +2 counts)
|
|
Power Display
|
Watts, VA, VAR
Ranges: 250 W, 2.50 kW, 25.0 kW, 250 kW, 2.50 MW, 250 MW
Accuracy: ±(4% + 4 counts)
Power Factor, PF
Displacement Power Factor, DPF
Range: 0.00 to 0.25 Accuracy: Not specified
Range: 0.25 to 1.0 Accuracy: ±0.04
|
|
Harmonics Display
|
Voltage
Ranges: 1st to 51st harmonic
Accuracy: ±(3% +2 counts) to ±(15% +5 counts)
Current
Ranges: 1st to 51st harmonic
Accuracy: ±(3% +8 counts) to ±(5% +8 counts)
Power
Ranges: 1st to 51st harmonic
Accuracy: ±(5% +2 counts) to ±(30% +5 counts)
Line frequency
Ranges: 40 Hz to 70 Hz fundamental
Accuracy: ±0.25 Hz
Phase
Ranges: 2nd to 51st harmonic
Accuracy: ±3 ¼ to ±15 ¼
K-factor
Ranges: 1.0 to 30.0
Accuracy: ±10%
|
|
Sags and Swells Recording
|
Recording times: 4 min to 16 days (selectable)
True-rms voltage:
Ranges: 5.000V, 50.00V, 500.0V, 1250V*
Accuracy: ±(2% +10 counts)
True-rms current
Ranges: 50.00A, 500.0A, 5.000 kA, 50.00 kA
Accuracy: ±(2% +10 counts)
|
|
Other Recording
|
Recording times: 4 min to 16 days (selectable)
Parameters:
Choose up to two from one of the groups below
V/A/Hz: Line voltage, current, frequency
Power: Watts, VA, VAR, PF, DPF, frequency
Harmonics: THD, harmonic voltage, (or current, or power), frequency,
% of total, phase
Ohms: Ohms, diode, continuity, capacitance
Temperature: Temperature
Scope: DC voltage, dc current, ac voltage, ac current, frequency,
pulse width, phase, duty cycle, peak max, peak min, peak min-max,
crest factor
|
|
Transient Capture
|
Minimum pulse width: 40 ns
Voltage threshold settings: 20%, 50%, 100%, 200% above or below
normal voltage
Min voltage and max voltage at cursor:
Ranges: 10V, 25V, 50V, 125V, 250V, 500V, 1250V
Accuracy: ±5% of full scale
|
|
Inrush Capture
|
Current ranges: Ranges: 1A, 5A, 10A, 50A, 100A, 500A,
1000A
Inrush times: Ranges: 1s, 5s, 10s, 50s, 100s, 5 min
Cursor readings, Current at cursor
Ranges: 12.5A, 25A, 50A, 125A, 250A, 500A, 1250A, 2500A, 5 kA
Accuracy: ±5% of full scale
Time between cursors
Ranges: 4 to 235 pixels (1 pixel = inrush time/250)
Accuracy: ±(0.2% + 2 pixels)
|
|
Scope Display
|
Time ranges: Ranges: 20 ns/div to 60 s/div
Max sampling rate: Ranges: 25 MS/s
Bandwidth:
Voltage channel [1]: 20 MHz at inputs, 1 MHz with TL24 Leads
Current channel [2]: 15 kHz at inputs, 10 kHz with 80i-500s Probe
Coupling: AC, DC
Vertical sensitivity: Ranges: 5 mV/div to 500V/div
Vertical resolution: 8 bit (256 levels)
Record length: 512 samples per channel
Timebase modes: Normal, roll, single
Pre-trigger: Up to 10 divisions
Measurements: dc, ac, ac+dc, peak, peak-peak, frequency, duty cycle,
phase, pulse width, crest factor
|
|
Ohms, Diode,Continuity
|
Ohms:
Ranges: 500.0W, 5.000 kW, 50.00 kW, 500.0 kW, 5.000 MW, 30.00 MW
Accuracy: ±(0.6% +5 counts)
Diode voltage: Accuracy: ±(2% +5 counts)
Continuity: Beeper on at < (30W ±Û5W)
Max current: 0.5 mA
Capacitance:
Ranges: 50.00 nF, 500.0 nF, 5.000 µF, 50.00 µF, 500.0 µF
Accuracy: ±(2% +10 counts)
Temperature**
Ranges: -100.0 ¼C to 400.0 ¼C, -200.0 ¼F to 800.0 ¼F
Accuracy: ±(0.5% +5 counts)
|
|
Screen Memories
|
10
|
|
Optically Isolated RS-232 Interface
|
To printer:
Supports HP Laserjet®, Deskjet®, Epson
FX/LQ and Postscript printers with optional PAC91 Printer Adapter
Cable
To PC:
FlukeView® Power Quality Analyzer Software included
|
|
FlukeView Power Quality Software
|
Hardware requirements:
PC or 100% compatible with Windows® 3.1, Windows®
95, or Windows NT® . Enough RAM for Windows operating
system. 4 MB hard drive space. Pointing device (mouse) recommended.
|
|
|
|
 |
|